Identification Of L G Fault Transients Capacitors Switching Engineering Essay

Published: November 21, 2015 Words: 2040

In a Electrical power system, whenever the voltage level goes below the desired level, there is need to improve the voltage profile. This increasing voltage can be obtained by using capacitor bank/s, as switching ON a capacitor bank/s causes increase in voltage while switching OFF a capacitor bank/s causes decrease in voltage. But these switching actions, if not specifically controlled give rise to transients which are undesirable and hazardous for the power system.

This paper introduces a voltage disturbance detection approach based on wavelet transform. The proposed approach (1) Identifies voltage disturbances, and (2) discriminates the type of event which has resulted in the voltage disturbance, e.g. either a fault or a capacitor-switching incident. Feasibility of the proposed disturbance detection approach is demonstrated based on digital time-domain simulation of a distribution power system using the PSCAD software package. Finally by using wavelet transform discriminates the type of event on the basis of energy levels.

Keywords: Capacitor Switching, L-G, distribution system, transient analysis, PSCAD wavelet transform.

I.INTORDUCTION

In the early days of development of the power system, electrical engineers were mainly concerned about 'keeping the lights ON'. They designed the power system to withstand outages. The main concern was to prevent the frequency of power system from deviating from 50 Hz after outages.

With the development in technology, use of gadgets like computers, arc furnaces, photo copier machines etc. increased. Due to the use of these devices the load on the power system increases especially during the day time because of which many a times voltage level decreases and is needed to be increased. This task of increasing the voltage profile is done by switching ON of a capacitor bank in the power system. But this switching action gives rise to capacitor switching transients. L-G faults are most common of all the faults viz. L-L, L-L-G, L-L-L faults and introduces transients in the current and voltage waveforms. These transients are very hazardous to the power system as they cause severe problems to it and components present in it. For instance, at any moment it can crash the computer or data loss and other such problems. So it becomes necessary to know the cause of these transients so that they can be suppressed. With the advent of computers, it becomes easier to simulate a power system in various software's available for simulation. Today, various simulation software's like EMTP, ATP, PSCAD (Power System Computer Aided Design) are available in the market.

In this paper, 'THE IEEE 5 BUS SYSTEM' is considered and it is simulated in PSCAD. The data obtained from the simulation is exported to the Wavelet Toolbox of MATLAB (db4 is used for analysis) is for acquiring the various parameters like voltage and energy level of the waveform obtained in PSCAD.

II. PROPOSED DISTURBANCE DETECTION SCHEME

Fig. 1 shows block diagram of the proposed disturbance detection scheme. It is composed of four main blocks; error signal generation, error signal analysis using wavelet, feature extraction ,and decision making. Function of the error signal generation block is to extract the superimposed disturbances on the fundamental component of system voltages. This provides an error signal which is later analyzed using wavelet transform. Outputs of the wavelet transform are inputs to the feature extraction block which identifies specific signatures of the disturbances in the system. Finally, the decision making block discriminates various types of disturbances based on the error signal and the calculated features.

2.1Error Signal Generation

The error signal generation block extracts the superimposed distortions on the measured voltages

The error signal is obtained by subtracting the fundamental component from the input signal.

Fig1: Proposed Disturbance Detection Scheme

2.2 Wavelet Transform Analysis

The wavelet analysis block transforms the error signal into different time-frequency scales. The wavelet transform provides information about the frequency content of a signal similar to the Fourier Transform (FT). However, contrary to the FT, wavelet transform is able to focus on short time

intervals for high-frequency components and long intervals for low-frequency components, thus making it a well suited tool for analyzing high-frequency transients in the presence of low-frequency components. Wavelet transform is inherently more appropriate for non stationary and non periodic wide-band signals.

The wavelet transform of a continuous signal is:

(1)

The values of wavelet coefficients F(a,b) represent the projection of f(t) along . Assume the center and width of function Ψ(t) is zero and ∆t in time domain, and zero and ∆w in frequency domain. Then, the function is centered at b and has width of a∆t in time domain and (1/a)∆w in frequency domain. To avoid generating redundant information, the base functions are generated discretely by selecting a=a0m and b = nb0 a0m

Where, a0 and b0 are fixed constants with a0 > 1and b0 > 0,m,n ε , and is the set of integers. Setting a0and b0 to 2 and 1 respectively results in an orthonormal basis of L 2 (IR) which is called dyadic- orthonormal wavelet transform. With this orthonormal basis, an algorithm of decomposing a signal into different time-frequency scales can be used which is called Multiresolution Signal Decomposition (MSD).

2.3 Properties of Mother Wavelet

Wavelet are families of functions generated form one single function, called as an analyzing wavelet or mother wavelet.

The mother wavelet must have the following properties

It must be oscillatory,

It must quickly decay to zero

It must have a zero average

It must be band pass

It must be integrate to zero

The iterative wavelet method for system converges rapidly for cases of interest in power engineering.

Fig 2:- Realization of wavelet transforms using a filter bank.

2.4 Feature Extraction

The purpose of feature extraction block is to identify specific signatures of the disturbances in the system. For example, a short circuit and a capacitor-switching incident result in disturbed voltages with different features. The wavelet transform breaks down the error signal into different time-frequency scales. Each scale represents the error signal in the corresponding band. The energy content of the scale signals relative to the error signal changes depending upon the type of disturbance. Therefore, the relative amplitudes of the scale signals with respect to the error signal are selected as the discriminating features.

Decision Making

A function of decision making block is to discriminate type of disturbances (L-G fault and Capacitor switching) as precisely as possible. The characteristic of each disturbance, example a fault, Capacitor switching, depends on several factors for example (1) type of event, e.g. single-phase-to-ground or phase-to-phase fault,(2) location of the event, (3) time instant of event and (4) network configuration.

In the decision making block, a probability functions is defined for the features, and the decisions is made using the maximum linked (ML) criteria. This method is used here to discriminate various type of disturbances in a power system.

III SIMULATION OF CIRCUIT IN PSCAD

A For L-G Fault at Bus 5

Fig. 3 For L-G Fault at Bus 5

B For Back to Back Capacitor Switching at Bus 5

Fig. 4 For Back to Back Capacitor Switching at Bus 5.

Fig. 5 For Isolated Capacitor Switching at Bus 5.

IV VOLTAGE WAVEFORM

Fig 6 Voltage at Bus 5 due to L-G Fault at Bus 5

Figure 7 Voltage at Bus 5 due to Back to Back capacitor switching at Bus 5

.

Fig 8 Voltage at Bus 5 due to Isolated capacitor switching at Bus 5

V METHOD TO DISTINGUISH BETWEEN CAPACITOR SWITCHING TRANSIENTS & OTHER TRANSIENTS

One of the prime methods to distinguish between different types of transients i.e. Capacitor Switching & Fault transients is to use their energy content as the differentiating factor. We have to feed the data of transients into the wavelet toolbox of MATLAB and on the basis of energy content in 1st & 2nd Decomposition level, we can judge which type of switching action has caused the Transients. Energy content can be calculated by using the formula:

Energy = ∫ ІE (t) І 2 dt

After the analysis in MATLAB the d1 & d2 for a LG fault is very hazardous as compared to that of Capacitor Switching Transients. Hence the energy threshold level of LG Fault for the given IEEE 5 BUS system is taken to distinguish between LG Fault Transients & Capacitor Switching Transients. Also the analysis for Back to Back Capacitor Switching & Isolated Capacitor Switching showed that the Energy threshold is higher for Back to Back Capacitor Switching. Hence this method can also be used to distinguish the Transients due to Back to Back Capacitor Switching & Isolated Capacitor Switching.

VI RESULT ANALYSIS IN MATLAB

PSCAD work is now exported to the MATLAB's Wavelet toolbox. The analysis for IEEE 5 Bus System with LG Fault at Bus No 5, Back to Back Capacitor Switching at Bus No.5 & Isolated Capacitor Switching at Bus No 5 is done with sampling Frequency 10 KHz.

Fig 9 Voltage at Bus 5 due to L-G Fault at Bus 5

Fig 10 Energy Levels at all Buses due to L-G Fault at Bus 5

Fig 11 Histogram Showing Comparative Energy Level of three phases

Fig 12 Voltage at Bus 2 due to Back to Back capacitor Switching at Bus 5

The three different rows correspond to the three phases of the input signal. The first row shows the Input signal from the PSCAD in the duration of 0.95 to 1.1 sec. d1, d2, d3, d4 & d5 gives the different decomposition levels. The wave a5 gives the approximated wave after the removal of 5 different frequency components from the input signal. From the above figure 10.12 it is clearly observed that the transients are present in d1 to d5 level of decomposition.

Fig 13 Voltage at Bus 3 due to Back to Back capacitor switching at Bus 5

Fig 14 Voltage at Bus 5 due to Back to Back Capacitor switching at Bus 5

By running this simulation we observed that due to Back to Back capacitor switching at Bus.5 , transients were observed on Bus No 2,3,5.

Now the Next diagram ( Fig 15) show the Energy Distribution for different decomposition levels

Fig 15 Energy Levels at all Buses due to Back to Back Capacitor Switching at Bus 5

Fig 16 Voltage at Bus 3 due to Isolated capacitor switching at Bus 5

Fig 17 Voltage at Bus 4 due to Isolated capacitor switching at Bus 5

Fig 18 Voltage at Bus 5 due to Isolated capacitor switching at Bus 5

Now the Next diagram (Fig 19 ) show the Energy Distribution for different decomposition levels.

Fig 19 Energy Levels at all buses due to Isolated Capacitor Switching at bus 5

VII RESULTS

Energy Content of Bus 5 with isolated Capacitor Switching is 0.0017 & 3.7723 Ã-10 -4 for d1&d2 level decomposition while for Back to Back Capacitor Switching is 4.2706 & 2.6752.

Energy Content of Bus 5 with isolated Capacitor Switching is 0.0017 & 3.7723Ã-10 -4 for d1&d2 level decomposition while for L-G Fault is 8.5568 & 4.5625.

VIII CONCLUSIONS

The paper introduces a voltage detection scheme for Power Quality applications. The scheme is based on Wavelet Transform.

With the Simulation of IEEE 5 BUS system Capacitor Switching Circuit & LG Fault circuit in PSCAD & further analysis in MATLAB. The Following Conclusions were Recorded:

Energy of the Transient produced due to Capacitor Switching depends on the magnitude of Capacitor being Switched ON along with the instant of Switching.

Energy content of LG fault is more than that of a Capacitor Switching. Hence by analyzing the energy content of transients the cause of production of Transients can be predicted.

Presence of Capacitor in the network prohibits the Transients from entering into the system by providing them a path of less reactance through it. But this causes excessive heating of that Capacitor Bank & is one of the major reasons for frequent blowing up of the Capacitor Banks at the utilities.

This method (simply identifying Voltage Waveform) introduced new technique to identify the Transients due to capacitor switching and faults. The salient features of the new technique are:

Rapid Voltage disturbance detection

Capability to identify the type of transient event which has caused voltage disturbance.

Performance of the new scheme is evaluated based on digital time-time domain simulation of a power distribution system, using the PSCAD.